Engineering Utility
Cable Sizing Calculator
Calculate the minimum cable cross-section based on load current, voltage drop, installation method, and ambient temperature. Results follow IEC 60364-5-52 and IEC 60228 standards.
Input Parameters
Results will appear here
Fill in the parameters on the left and click Calculate Cable Size to get your recommendation.
Quick Reference
| Section | Cu XLPE (A) | Al XLPE (A) |
|---|---|---|
| 1.5 mm² | 18 | 14 |
| 2.5 mm² | 25 | 19 |
| 4 mm² | 34 | 26 |
| 6 mm² | 43 | 33 |
| 10 mm² | 60 | 46 |
| 16 mm² | 80 | 61 |
| 25 mm² | 101 | 78 |
| 35 mm² | 122 | 94 |
| 50 mm² | 144 | 110 |
| 70 mm² | 184 | 141 |
| 95 mm² | 223 | 171 |
| 120 mm² | 259 | 199 |
| 150 mm² | 295 | 227 |
| 185 mm² | 341 | 262 |
| 240 mm² | 403 | 309 |
IEC 60364-5-52 Table B.52.4 · Method B2 · 3-core · 30°C
Standard Basis
IEC 60364-5-52 · IEC 60228 · BS 7671 (18th Ed.)
Calculation Method
Current capacity + voltage drop check with temperature derating
Need a Custom Spec?
Our engineers can assist with complex installations -- contact us.