XLPE Power Cables · IEC 60502 · Ships from stock

Technical Reference

Cable Ampacity Tables

Current-carrying capacity reference for copper and aluminum conductors under standard installation conditions. Values based on IEC 60364-5-52 and GB/T 16895.6. Derate for ambient temperature, grouping, and burial depth per project requirements.

Request Full Datasheet

Engineering Note: All ampacity values are for single-circuit operation at 30 °C ambient (air) / 20 °C (ground), soil resistivity 1.0 K·m/W. Apply correction factors for actual site conditions. Values shown are for 3-core or 3-phase single-core cables. Consult our technical team for derating calculations.

Filter Parameters

Showing all 20 conductor sizes

Table A1

Copper Conductor · XLPE Insulation · In Air (Free) · 0.6/1 kV

IEC 60364-5-52 Method B2 / E
Section (mm²)ClassSingle-Core (A)3-Core (A)4-Core (A)Max Temp (°C)Resistance (mΩ/m)Notes
1.5Class 1/22622209012.10--
2.5Class 1/2363027907.41--
4Class 1/2494037904.61--
6Class 1/2635146903.08--
10Class 1/2867063901.83--
16Class 1/21159485901.15--
25Class 1/2149119107900.727--
35Class 1/2185148133900.524--
50Class 1/2225180162900.387--
70Class 1/2289232209900.268--
95Class 1/2352282254900.193--
120Class 1/2410328295900.153--
150Class 1/2473379341900.124--
185Class 1/2542434391900.0991--
240Class 1/2641514463900.0754--
300Class 1/2741593534900.0601--
400Class 1/2868694--900.0470Single-core only for 4-core
500Class 1/2982----900.0366Single-core only
630Class 1/21,138----900.0283Single-core only
800Class 1/21,318----900.0221Single-core only

Table A2

Copper Conductor · XLPE Insulation · Direct Buried · 0.6/1 kV

IEC 60364-5-52 Method D1
Section (mm²)ClassSingle-Core (A)3-Core (A)4-Core (A)Max Temp (°C)Burial Depth (m)Notes
10Class 1/2958072900.7--
16Class 1/212010090900.7--
25Class 1/2152127114900.7--
35Class 1/2183153138900.7--
50Class 1/2216181163900.7--
70Class 1/2268224202900.7--
95Class 1/2320268241900.7--
120Class 1/2363304274900.7--
150Class 1/2408342308900.7--
185Class 1/2457383345900.7--
240Class 1/2526441397900.7--
300Class 1/2598502452900.7--

Table B1

Aluminum Conductor · XLPE Insulation · In Air (Free) · 0.6/1 kV

IEC 60364-5-52 Method E
Section (mm²)ClassSingle-Core (A)3-Core (A)4-Core (A)Max Temp (°C)Cu Equiv. FactorNotes
16Class 1/2877265900.78Min. 16 mm² for Al
25Class 1/21149384900.78--
35Class 1/2141116104900.78--
50Class 1/2172141127900.78--
70Class 1/2220180162900.78--
95Class 1/2267219197900.78--
120Class 1/2309253228900.78--
150Class 1/2356292263900.78--
185Class 1/2407334301900.78--
240Class 1/2480394355900.78--
300Class 1/2551452407900.78--

Table C1 -- Comparison

Copper Conductor · XLPE vs PVC Insulation · In Air · 0.6/1 kV

IEC 60364-5-52
Section (mm²)XLPE 3-Core (A)PVC 3-Core (A)XLPE AdvantageXLPE Max TempPVC Max TempRecommendation
107057+23%90 °C70 °CXLPE preferred
2511996+24%90 °C70 °CXLPE preferred
50180145+24%90 °C70 °CXLPE preferred
95282226+25%90 °C70 °CXLPE preferred
185434344+26%90 °C70 °CXLPE preferred
300593468+27%90 °C70 °CXLPE preferred

Correction / Derating Factors

Apply these multipliers to tabulated ampacity values for non-standard installation conditions.

Ambient Temperature (Air) -- XLPE 90 °C

Ambient (°C)Factor
251.04
30 (base)1.00
350.96
400.91
450.87
500.82
550.76
600.71

Cable Grouping -- In Air / On Tray

No. of CircuitsTouchingSpaced
11.001.00
20.800.85
30.700.79
40.650.75
50.600.72
60.570.69
7-90.540.66
10-120.500.63

Ground Temp & Soil Resistivity -- Buried XLPE

Ground Temp (°C)Factor
101.10
151.05
20 (base)1.00
250.95
300.89
350.84

Soil Thermal Resistivity (K·m/W)

ResistivityFactor
0.7 (wet)1.08
1.0 (base)1.00
1.50.90
2.00.83
3.0 (dry)0.72

Standards & Reference Basis

IEC 60364-5-52

Wiring system selection and erection. Primary reference for installation methods and ampacity tables.

IEC 60502-1/2

Power cables with extruded insulation up to 30 kV. Conductor, insulation, and sheath requirements.

GB/T 12706-1/2/3/4

Chinese national standard for power cables up to 35 kV with XLPE and PVC insulation.

IEC 60287

Electric cables -- Calculation of the current rating. Basis for all ampacity computation methodology.

Need Project-Specific Calculations?

Our engineers provide free derating and cable sizing support.

Submit your installation parameters -- ambient temperature, grouping, burial depth, load profile -- and receive a compliant sizing report within 1 business day.